61kW COP 3.38 high efficiency air cooled modular chiller / heat pump units
Specifications:
EKAC modular air-cooled heat pump units combines more than 40 years of Italian air-cooled heat pump design experience and the application practices of modular units in China, so as to meet customers' requirements on product efficiency, safety, smartness and comfort. This series of units have diversified models and are applicable to various environments, such as villas, hotels, recreation centers, hospitals, dining halls, office buildings, supermarkets, and various industrial processes that requires cooling.
Technical data sheet
Model |
|
EKAC 210B |
EKAC 210BR |
EKAC 420B |
EKAC 420BR |
EKAC 630B |
EKAC 630BR |
Unit combination |
Master unit |
EKAC 210BM |
EKAC 210BRM |
EKAC 210 BM |
EKAC 210BRM |
EKAC 210BM |
EKAC 210BRM |
slave unit |
-- |
-- |
EKAC 210BS |
EKAC 210BRS |
2EKAC 210BS |
2EKAC 210BRS |
Nominal cooling capacity |
kW |
61 |
61 |
122 |
122 |
183 |
183 |
USRT |
17.35 |
17.35 |
34.70 |
34.70 |
52.04 |
52.04 |
×104kcal/h |
5.25 |
5.25 |
10.49 |
10.49 |
15.74 |
15.74 |
Nominal heating capacity |
kW |
-- |
64 |
-- |
128 |
-- |
192 |
USRT |
-- |
18.20 |
-- |
36.4 |
-- |
54.6 |
×104kcal/h |
-- |
5.50 |
-- |
11.0 |
-- |
16.5 |
Total power of nominal cooling capacity |
kW |
18.0 |
18.0 |
36.0 |
36.0 |
54.0 |
54.0 |
Total power of nominal heating capacity |
kW |
-- |
16.8 |
-- |
33.6 |
-- |
50.4 |
Power supply |
|
380V/3N~/50Hz |
Refrigerant |
Type |
|
R22 |
Control |
|
Electronic expansion valve |
Compressor |
Type |
|
Fully hermetic volute compressor |
Lubricant |
|
Mineral oil (SUNISO 3GS) |
Qty. |
Set |
2 |
2 |
4 |
4 |
6 |
6 |
Fan |
Type |
|
High-efficiency vacuum braze-welded panel type |
Qty. |
Set |
2 |
2 |
4 |
4 |
6 |
6 |
Water side heat exchanger |
Type |
|
High-efficiency vacuum braze-welded panel type |
Water flow for
cooling |
3
m /h |
10.5 |
10.5 |
21.0 |
21.0 |
31.5 |
31.5 |
Water flow rate
in heating mode |
3
m /h |
-- |
11.0 |
-- |
22.0 |
-- |
33.0 |
Water resistance |
kPa |
43 |
43 |
43 |
43 |
43 |
43 |
Recommended diameter for general inlet/outlet water pipe |
inch |
≥2 |
≥2 |
≥3 |
≥3 |
≥3 |
≥3 |
Power cable specification |
Section area of live line |
2
mm |
≥10 |
≥10 |
≥35 |
≥35 |
≥70 |
≥70 |
Qty. of live lines |
|
3 |
Section area of null line |
2
mm |
≥4 |
Qty. of null lines |
|
1 |
Section area of grounding line |
2
mm |
≥10 |
≥10 |
≥16 |
≥16 |
≥35 |
≥35 |
Qty. of grounding lines |
|
1 |
Dimensions |
L x H |
mm |
2012×1840 |
Width |
mm |
880 |
880 |
2125 |
2125 |
3370 |
3370 |
Unit weight |
Net weight |
kg |
500 |
520 |
1000 |
1040 |
1500 |
1560 |
Operating weight |
kg |
510 |
530 |
1020 |
1060 |
1530 |
1590 |
Model |
|
EKAC 840B |
EKAC 840BR |
EKAC 1050B |
EKAC 1050BR |
EKAC 1260B |
EKAC 1260BR |
Unit combination |
Master unit |
EKAC 210BM |
EKAC 210BRM |
EKAC 210BM |
EKAC 210BRM |
EKAC 210BM |
EKAC 210BRM |
slave unit |
3EKAC 210BS |
3EKAC 210BRS |
4EKAC 210BS |
4EKAC 210BRS |
5EKAC 210BS |
5EKAC 210BRS |
Nominal cooling capacity |
kW |
244 |
244 |
305 |
305 |
366 |
366 |
USRT |
69.39 |
69.39 |
86.74 |
86.74 |
104.09 |
104.09 |
×104kcal/h |
20.98 |
20.98 |
26.23 |
26.23 |
31.47 |
31.47 |
Nominal heating capacity |
kW |
-- |
256 |
-- |
320 |
-- |
384 |
USRT |
-- |
72.8 |
-- |
91.0 |
-- |
109.2 |
×104kcal/h |
-- |
22.0 |
-- |
27.5 |
-- |
33.0 |
Total power of nominal cooling capacity |
kW |
72.0 |
72.0 |
90.0 |
90.0 |
108.0 |
108.0 |
Total power of nominal heating capacity |
kW |
-- |
67.2 |
-- |
84.0 |
-- |
100.8 |
Power supply |
|
380V/3N~/50Hz |
Refrigerant |
Type |
|
R22 |
Control |
|
Electronic expansion valve |
Compressor |
Type |
|
Fully hermetic volute compressor |
Lubricant |
|
Mineral oil (SUNISO 3GS) |
Qty. |
Set |
8 |
8 |
10 |
10 |
12 |
12 |
Fan |
Type |
|
High-efficiency vacuum braze-welded panel type |
Qty. |
Set |
8 |
8 |
10 |
10 |
12 |
12 |
Water side heat exchanger |
Type |
|
High-efficiency vacuum braze-welded panel type |
Water flow for
cooling |
3
m /h |
42.0 |
42.0 |
52.5 |
52.5 |
63.0 |
63.0 |
Water flow rate
in heating mode |
3
m /h |
-- |
44.0 |
-- |
55.0 |
-- |
66.0 |
Water resistance |
kPa |
43 |
43 |
43 |
43 |
43 |
43 |
Recommended diameter for general inlet/outlet water pipe |
inch |
≥4 |
≥4 |
≥4 |
≥4 |
≥5 |
≥5 |
Power cable specification |
Section area of live line |
2
mm |
≥95 |
≥95 |
≥120 |
≥120 |
≥150 |
≥150 |
Qty. of live lines |
|
3 |
Section area of null line |
2
mm |
≥4 |
Qty. of null lines |
|
1 |
Section area of grounding line |
2
mm |
≥50 |
≥50 |
≥60 |
≥60 |
≥75 |
≥75 |
Qty. of grounding lines |
|
1 |
Dimensions |
L x H |
mm |
2012×1840 |
Width |
mm |
4615 |
4615 |
5860 |
5860 |
7105 |
7105 |
Unit weight |
Net weight |
kg |
2000 |
2080 |
2500 |
2600 |
3000 |
3120 |
Operating weight |
kg |
2040 |
2120 |
2550 |
2650 |
3060 |
3180 |
Note:
■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.
■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature
7°C/6°C.
■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK
does not provide the pipes.
■ Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists
the parameters for common module combinations.
■ For on-site electric wiring, see the name plate or installation menu of the unit.
Description
1. Based on its leading-edge design for air cooled and heat pump units in Europe as well as the wide use of its air-cooled units in China, EK has launched this series of innovative modular air-cooled water chiller (heat pump) units. The full-load COP of this series is higher than that the energy saving product certification standard
2. Each modular unit has two power gears. When multiple modular units are combined, there could be many power gears. Fully-optimized model selection and matching practice ensures that the units can always save as much energy as possible. When operating with a partial load (99% of full operation time), the EER is even 4% higher.
3. With an optional 2-way valve water control feature, the unit can send out signals to turn off corresponding chilled water valves. This enables automatic flow control for pumps in line with the transducer, which helps save more energy.
4. The unit features modul